Effective metal shields of high voltage distribution cable lines

Ljubivoje M. Popovic

Abstract


The presented methodology enables determining induced currents and voltages relevant to the correct estimation of security conditions required in operating and maintenance of the metal installations surrounding high-voltage distribution cable lines. It is based on the on-site measurements of currents appearing in two phase conductors of the considered cable line during a simulated ground fault in the supplied substation. Their values are utilized to compensate for the deficiency of all relevant but unknown data concerning the surrounding metal installations. It was done by introducing an equivalent cable shield substituting, from the standpoint of inductive influence, all surrounding metal installations. Here is shown that this equivalent shield can be determined in such a way that it becomes identical from the standpoint of its appearance to the actual cable line shield but with a changed value of its longitudinal resistance. When this value is determined for single-core cables belonging to a certain cable line it becomes possible to determine the actual reduction factor, inductive influence, and sequence impedance of the considered cable line by using a standard and well-known calculation procedure.


Keywords


ground fault; grounding system; inductive coupling; reduction factor; screening factor; series impedance

Full Text:

PDF


DOI: http://doi.org/10.11591/ijape.v12.i4.pp451-462

Refbacks

  • There are currently no refbacks.


Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.

International Journal of Applied Power Engineering (IJAPE)
p-ISSN 2252-8792, e-ISSN 2722-2624

Web Analytics Made Easy - StatCounter IJAPE Visitors