Condition assessment of medium voltage cable insulation using leakage current and phase-resolved partial discharge

Kamrai Janprom, Sittadach Morkmechai, Natchanun Prainetr, Supachai Prainetr

Abstract


Reliable operation of medium-voltage distribution networks critically depends on the integrity of cross-linked polyethylene (XLPE) insulated cables. This paper proposes a diagnostic methodology that integrates leakage current (LC) measurement with phase-resolved partial discharge (PRPD) analysis to assess cable insulation condition. A MATLAB R2025 simulation model is first developed to emulate partial discharge (PD) signals superimposed on leakage current, providing preliminary validation of the proposed approach. The method is then experimentally verified using a 70 mm² XLPE cable rated at 16/20 (24) kV and tested in accordance with IEC 60502. Under applied high-voltage stress, leakage current and PD activity are measured, and insulation degradation is characterized using PRPD patterns. Both simulation and experimental results confirm that the proposed method reliably detects insulation defects and provides accurate condition assessment of XLPE cables. These findings demonstrate the potential of the method as a practical tool for supporting condition-based maintenance in medium-voltage power distribution systems.

Keywords


cable XPLE; discharge; leakage current; medium voltage distribution; phase-resolved partial

Full Text:

PDF


DOI: http://doi.org/10.11591/ijape.v15.i3.pp1340-1350

Refbacks

  • There are currently no refbacks.


Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.

International Journal of Applied Power Engineering (IJAPE)
p-ISSN 2252-8792, e-ISSN 2722-2624

Web Analytics Made Easy - StatCounter IJAPE Visitors